- HV Total Energy Capacity [kWh] 40
- Energy, 80% DoD [kWh] 1 32
- Energy, 90% DoD [kWh] 1 36
- Max/Cont. Discharge Current [A] 2 150/100
- Max/Cont. Discharge Power [kW] 2 61/40
- Max & Cont. Charge Current [A] 100
- Nominal Voltage [V] 3 410
- Max/Min. Operating Voltage [V] 454/365
- Battery Dimensions – H x W x D [mm] 4 1260x740x290
- Crated Dimensions – H x W x D [mm] TBC
- Battery Weight [kg] 327
- Crated Weight [kg] TBC
- DC Connection – Fly Leads (no. per electrode) [mm²] 5 1 x 25mm² Permopower
Enclosure Aluminium enclosure painted white, for use indoors or fully protected under-cover environments, rated to IP20.
Protection Shunt Trip Circuit Breaker sized to suit max current, can be tripped by BMS if critical fault incl. overcurrent, cell under and over voltage, temperature, weak cell detection, minimum SoC control, manual reset.
Control Interface CAN Bus for diagnostics & troubleshooting. RJ45 Strictly for BMS & inverter communication.
Human Interface State of Charge display (0 to 100%), Error light, Error Reset button, USB plug for programming.
Warranty 6 10 years or 4 000 cycles for average 80% DoD, and max 90% DoD.
Service Life 6 10 year (or 4000 cycles) warranty for 80% average DoD, 13-15 yrs (>5 500 cycles) expected life at 70% DoD, 15-20 years at 50% DoD (>7 000 cycles).
Need more information?
See SPECIFICATIONS